HPL Raised Floor System
Experience enduring quality, breathtaking beauty, and style that captivates - perfect for those who settle for nothing less than perfection.

HPL Raised floor system
HPL raised floor system refers to a type of access flooring system that uses High Pressure Laminate (HPL) as its surface covering. Mainly used in the server rooms, school computers, data centers, etc.HPL Raised floor panels offer a combination of durability, functionality, and aesthetic appeal, making them a popular choice for modern building interiors that require adaptable flooring solutions.
Title | Property |
|---|---|
Panel dimension | 600 x 600 mm |
Thickness | 33 mm |
Top | HPL Surface Panel |
Core | aluminum honeycomb core filled with light cement |
Structure of the Panel
HPL Raised floor is a composite rasied movable floor with full metal and aluminum honeycomb structure inside. Filled with light cement and the margins are fixed with black conductive edge strip.
HPL Surface panel
Galvanzied steel sheet

Aluminum honeycomb core
Light Cement
1. Structure
The Panel typically consists of a steel top steel top sheet welded to a formed steel bottom sheet, filled with a lightweight cement mixture. This creates a strong, durable, and lightweight contruction.
2. Surface Material:
The top of the panel is covered with High Pressure Laminate(HPL), which is the most common surface covering used on access floors. HPL is a floor-grade lamincate that provides serveral benefits:
-
Static dissipation
-
Easy to clean and maintain
-
Durable walking surface
-
Anti-static properties
Key Features of HPL Panel Raised Floors:
Load Capacity:
HPL Raised floor panels are designed to handle various load requirement, typically ranging from 800 to 1500 lbs concentrated load.
Applications:
These panels are commonly used in commercial and industrial settings where underfloor access is required, such as offices, data centers, and other facilties that need flexible cable management and airflow systems.
5. Additional Features:
-
Fire - resistant and non - combustible
-
Waterproof
-
Corrosion - resistant
-
Long service life

Purpose and utility.

-
Supporting Data Center Equipment:
Data centers house heavy and sensitive equipment such as servers, routers, and switches. Raised floor panels provide a sturdy platform for this equipment, allowing easy access for maintenance, upgrades, and efficient cable management.
-
Enhancing Airflow and Cooling Efficiency:
Maintaining optimal temperatures in data centers is crucial to prevent equipment overheating. Raised floors enable underfloor air distribution, delivering cool air precisely where needed. This system works alongside HVAC (heating, ventilation, and air conditioning) systems, ensuring consistent and energy-efficient cooling, which directly impacts server rack performance and equipment longevity.

Installation Detail

Model | Concentrate Load | Impact Load | Ultimate Load | Uniform Load | Rolling Load (10 Times) | Rolling Load (1000 Times) |
|---|---|---|---|---|---|---|
HPL JS800 | ≥ 3596N / ≥807lbs | 670N / 150lbs | ≥10799N / 2425lbs | ≥19796N/M² / ≥4450lbs/M² | 2900N / 651lbs | 2500N / 562lbs |
HPL JS1000 | ≥ 4498N / ≥1000lbs | 670N / 150lbs | ≥13494N / 3033lbs | ≥23296N/M² / ≥5237lbs/M² | 3590N / 807lbs | 2950N / 663lbs |
HPL JS1250 | ≥ 5595N / ≥1256lbs | 670N / 150lbs | ≥16797N / 3776lbs | ≥33084N/M² / ≥7437lbs/M² | 4490N / 1009lbs | 3590N / 807lbs |
HPL JS1500 | ≥ 6695N / ≥1503lbs | 670N / 150lbs | ≥20092N / 4516lbs | ≥42583N/M² / ≥9573lbs/M² | 5500N / 1236lbs | 4490N / 1009lbs |
HPL JS2000 | ≥ 8890N / ≥1998lbs | 670N / 150lbs | ≥26680N / 5997lbs | ≥49783N/M² / ≥11191lbs/M² | 6600N / 1483lbs | 5590N / 1256lbs |
HPL JS2500 | ≥ 11092N / ≥2493lbs | 670N / 150lbs | ≥33292N / 7483lbs | ≥58281N/M² / ≥13101lbs/M² | 8800N / 1978lbs | 6690N / 1503lbs |
* Remark:
System Resistance 1x10⁵ - 1 x10⁹Ω |

*Tested by the world's leading Testin, Inspection and Certification
SGS S.A.